– 11 –
7. Calibration
P5/EP5 is when shipped from PMV pre-
calibrated for 90 ±0,5 deg rotation, (can also be
30, 45 or 60 deg, see installed cam).
For most applications the valve closed position
is more critical than valve open position,
most attention should be paid at valve closed
position. Always start calibration procedure by
applying 0 % input signal, then adjusting zero.
P5/EP5 is calibrated by turning thumb wheels 1
& 4.
Arrows on arm 5 indicate turning direction of
thumb wheels.
< “+“ = Increase zero/span
> “-“ = Decrease zero/span
Calibration procedure
Check cam seating, section 9 before starting
calibration procedure.
1.Apply 0 % input signal (0% = 20 kPa/3 psi
or 4 mA)
2.Wait for steady state.
3.Adjust zero by turning the silver (lower)
thumb wheel 4 with finger or with screw
driver 7 from the outside.
4.Apply 100% input signal (100% = 100 kPa/
15 psi or 20 mA)
5.Wait for steady state then memorize result.
6.Apply 0% input signal.
7.Adjust span if necessary. This is done by
first loosing screw 2, then turning the
yellow (upper) thumb wheel 1 “+“ or “-
and finally tighten screw 2. Spring top must
not be in contact with spring guide 3.
8.Check zero and adjust if needed.
9.Repeat steps 2 to 8 until desired calibration
is achieved.